Digital Monitoring Products Canadian XR100 Bedienerhandbuch Seite 73

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 78
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 72
XR100 Series Programming Guide Digital Monitoring Products
65
Appendix
21.11 Zone Type Specications
TheXR100Seriespanelcontainsmultipledefaultzonetypesforuseinconguringthesystem.These
zone types provide the most commonly selected functions for their applications. All zone types can be
customizedbychangingthevariableoptionslistedbelow.TheKeypadBusZoneInformationtablebelow
reectsthezonetypesforKeypadBusZones.TheXR100SeriesLX-BusZoneInformationtablebelow
reectsthezonetypesforLX-BusZones.
Keypad Bus Zone
Information
Type Area Fire
Bell
Disarmed
Open
Disarmed
Short
Armed
Open
Armed
Short
Swinger
Prewarn
Entry Delay
Retard Delay
Presignal
Fast Response
Cross Zone
Priority
Follow Area
Real-Time Rprts
Door Number
Style
Assign Disarm condition of NT,
DY, EX, A1, and A2 only
Assign Prewarn and Entry
Delay for EX only
Assign Retard and Presignal
for FI, SV, A1, and A2 only
Zone Type Defaults
--
DY
FI
EM
A1
FV
NT
EX
PN
SV
A2
AR
PERIM
INT
BDRM
or
1 to 8
Output *
Message
Output *
Action
Message
Output *
Action
Message
Output *
Action
Message
Output *
Action
A
T
L
-
D
S
S
P
M
F
A
T
L
-
D
S
S
P
M
F
A
T
L
-
D
S
S
P
M
F
A
T
L
-
D
S
S
P
M
F
N
or
Y
1
to
8
1
or
4
N
or
Y
1
to
8
N
or
Y
N
or
Y
N
or
Y
0
to
8
N
or
Y
0
to
8
TGL
ARM
DIS
STEP
MNT
Night NT - 0 S - 0 S A 0 S A 0 S Y N N N 0 N 0
Day DY T 0 S T 0 S A 0 S A 0 S Y N N N 0 N 0
Exit EX - 0 S - 0 S A 0 S A 0 S Y
1-8
1 N N N N 0
Fire FI 0 T 0 S A 0 S N N + N N N
Panic PN T 0 S A 0 S N N N N
Emergency EM T 0 S A 0 S N N N N
Supervisory SV 0 T 0 S A 0 S N N + N N N
Auxiliary 1 A1 T 0 S A 0 S T 0 S A 0 S N N + N N N 0 N 0
Auxiliary 2 A2 T 0 S A 0 S T 0 S A 0 S N N + N N N 0 N 0
Fire Verify FV 0 T 0 S A 0 S N N N
Arming AR TGL
Zone Name
*OutputOptions:1to6,450to474,480to499,500to599,D1toD8,G1toG20. + =SetretardtoYESbeforeselectingpresignal.=Zonefunctionsnotavailable.
21.11.1 Keypad Bus Zone Type Defaults
Thesearecompletespellingsoftheabbreviationsusedforthezonetypes,suchasNightandExit.
Type -Thesearetheabbreviationsusedforthezonetypes,suchasNTandEX.
Area-ForanAreasystemoraHome/Sleep/AwaywithGuestsystemthisis1to8.ForanAll/Perimeteror
Home/Sleep/Awaysystem,thisistheInterior,Bedroom,orPerimeter.SelecttheareaforNT,DY,EX,A1,
A2,andARtypes.
Fire Bell Out -OnlyavailableforFI,FV,andSVzones.Useanyoutputzonenumberlisted.
Message -A=alarmreport,T=troublereport,L=local,noreport,(dash)=noreport,D=door
propped(WhenSVzoneisconnectedto303Silence/ResetSwitch),S=sensorreset/alarmsilence,
C=earlymorningambushcancel.
Output -Theseare1to6on-boardand500to599off-boardrelayoutputs,450to474and480to499
wirelessoutputs,D1toD8,andG1toG20.
Action -Thisselectstheactionoftheoutput:S=steady,P=pulse,M=momentary,andF=follow
Swinger -Thezonecanbeautomaticallybypassedafteraprogrammednumberoftrips.
Prewarn -Thisselectsthekeypadaddressthatsoundstheentryprewarnforthiszone.
Entry Delay-Thisistheentrydelaytimerselectedasthedefaultforthiszone.
Retard Delay-Providesaprogrammedretardtimebeforeanalarminitiatesfromashortedzone.When
used on an arming zone, the retard delay occurs when the zone is shorted before the armed state has
changed. If the arming zone has Maintain as the Style, the retard delay also occurs when the zone returns
to a normal state.
Presignal -Providesakeypadtoneforzonesinretarddelay.RetardmustbeYESbeforePresignalcanbeselected.
Fast Response-Providesa167mszoneresponseinsteadofthenormal500msresponse.
Cross Zone-Providescrosszoningwithanyofthe574zones.
Priority -Requiresthiszonetobeinanormalconditionbeforetheareacanbearmed.
Style - The abbreviations for arming zone style:
TGL=Toggle,ARM=Armonly,DIS=Disarmonly,STEP=Wirelessarming,MNT=Maintain
Seitenansicht 72