Zone InformatIon
ARM AREAS: PERIM
InanAll/PerimeterorHome/Sleep/Awaysystem,thisspeciestheareatobe
armedbytheKeyFobbuttonbeingprogrammed.ForAll/Perimetersystems,
choosePERIMorALL,forHome/Sleep/AwayorHome/Awaysystems,choose
HOME,SLEEP,orAWAY.
Note:Areas3andhigherinanAll/Perimetersystem,andareas4andhigherina
Home/Sleep/Awaysystemarenotavailableforuse.
Afterselectingtheareas,forone-buttonkeyfobstheZoneNo.:optiondisplays.
Fortwo-buttonorfour-buttonkeyfobs,theKeyFobButtonSelectionoption
displays to program additional buttons.
18.11.10
OUTPUT NO: XXX
Output Number
YoucanspecifyarelayoutputtooperatewhenOUT(Output),PN(Panic),PN2
(Panic2),EM(Emergency),orEM2(Emergency2)isselectedforakeyfob
ButtonActionandthebuttonispressed.Validrangeis1to6,500to599,
D1toD8,orG1toG20.ForanoutputturnedonbyaPN,PN2,EM,orEM2
button action, the output turns off when any area is disarmed.
To enter an output number, press a top row Select key followed by the output
number. Press the COMMAND key.
18.11.11
ACTION: XXXXXXXX
Output Action
ThisoptionallowsyoutodenetheKeyFoboutputoperation(STD,MOM,TGL,
OFF)whenPN,PN2,EM,orEM2isselectedforaKeyFobButtonActionandthe
buttonispressed.ForanoutputturnedonbyaPN,PN2,EM,orEM2button
action, the output turns off when any area is disarmed by Key Fob button press.
The currently programmed action displays.
OUTPUT ACTION?
STD PLS MOM TGL
STD (Steady) - The output is turned on and remains on until the area is
disarmed, an output cutoff time expires, or the output is reset from the keypad
menu.
PLS (Pulse) - The output alternates one second on and one second off. Note:
ThepulsingrateforaModel716relayattachedtotheLX-Busis1.6seconds.
MOM (Momentary) - The output is turned on only once for one second.
TGL (Toggle) - The output alternates between the armed and disarmed
condition. When restored to normal, no action occurs. When the zone opens
fromanormal(disarmed)state,atroubleisreported.Whenopenedfroma
shorted(armed)state,analarmisreportedandthezoneisdisableduntilthe
area(s)isdisarmedfromeitherakeypadorRemoteLink.
OUTPUT ACTION?
OFF
OFF (Off) - The output is turned off. If programmed, the output was turned
on by some other means such as another button press, a zone action, or a
schedule.
18.11.12
NEXT ZONE NO YES
Next Zone
SelectYEStoreturntotheZONENO:-optiontoprogramanewzone.SelectNO
to display the Alarm Action option.
Note: All wireless programming is stored in the XR500 Series panel. The 1100X
Wireless Receiver obtains the necessary programming information from the
panel each time the receiver powers up, when the programmer STOP routine
is selected or the panel is reset. The receiver memory refresh takes up to 10
seconds to complete depending on the number of wireless zones programmed
andtheRedLEDremainsonduringthistime.Normalreceiveroperationis
inhibited during the memory refresh period.