Digital Monitoring Products XR150/XR350/XR550 Series Programming Guide
24
SYSTEM OPTIONS
System Options
9.1 System Options
This section allows you to select system-wide parameters.
9.2 System
This option allows you to program how the areas operate for arming and disarming. The
options you can choose are listed below:
AREA - All 32 areas can be programmed and operated independently.
ALL/PERIMETER - Area 1 is the Perimeter and Area 2 is the Interior.
HOME/SLEEP/AWAY - Area 1 is the Perimeter, Area 2 is the Interior, and Area 3 is the
Bedrooms. With the HOME/SLEEP/AWAY option, the user can:
• 1. Select HOME to arm just the perimeter.
• 2. Select SLEEP to arm the perimeter and interior (non bedroom areas).
• 3. Select AWAY to arm all three areas.
Note: A Home/Sleep/Away system can be congured to use all three areas or only use the
Home and Away areas.
HOME/SLEEP/AWAY WITH GUEST- This allows the alarm system to be divided into a main
house HOME/SLEEP/AWAY system and two other guest houses that also are set up as HOME/
SLEEP/AWAY systems.
Areas 1, 2, and 3 are the Perimeter, Interior, and Bedrooms for the Main house system.
Areas 4, 5, and 6 are the Perimeter, Interior, and Bedrooms for the Guest 1 house system.
Areas 7, 8, and 9 are the Perimeter, Interior, and Bedrooms for the Guest 2 house system.
These areas are automatically assigned per system and cannot be changed. See Display
Areas in Device Setup to assign keypads to a system. Zones are assigned to a system by
assigning the system’s area numbers to the zone in Zone Information programming.
When either All/Perimeter or Home/Sleep/Away is selected, the area names are
automatically assigned and cannot be modied.
Note: Areas 3-32 in an All/Perimeter system, areas 4-32 in a Home/Sleep/Away system,
and areas 9-32 in a Home/Sleep/Away with Guest system are not available for use and are
initialized.
9.3 Instant Arming
When YES is selected, the arming keypad displays INSTANT for selection during the exit
countdown delay when arming fewer than all areas of the system. At the time instant
arming is selected, any entry and exit delays programmed for the areas being armed are
ignored. The entry delay for previously armed areas is not affected by instant arming.
When NO is selected, INSTANT does not display during arming. Default is NO for an Area
System, and YES for an All/Perimeter or Home/Sleep/Away system.
9.4 Closing Wait
When YES is selected, the keypad displays ONE MOMENT... while waiting for an
acknowledgement from the receiver before arming the selected area(s) and performing a
Bell Test (if selected). Exit delays begin after the Closing Wait. Opening/Closing reports
must be YES to enable Closing Wait.
9.5 Entry Delay 1
Enter the Entry Delay time for all Exit type zones programmed to use Entry Delay 1. When
an armed Exit type zone is faulted, the keypad prewarn tone begins sounding. All keypads
programmed to prewarn for that zone display ENTER CODE:- and the name of the zone
causing the entry delay. When the rst digit of a code is entered, the prewarn tone stops
at that keypad. If an invalid code is entered, the prewarn tone begins sounding again. The
area must be disarmed before the delay expires or an alarm report is sent to the receiver
and an alarm sounds. All zones in that area are delayed along with the Exit zone. Entry
Delay times can be from 30 to 250 seconds. Repeat the above for each entry delay being
used in the system.
Note: Specic Exit Error operation is based on the Entry Delay used (1-4) with an EX type
zone. See Exit Delay.
Note: For UL Installations, the combined Transmit Delay (Abort Window) and Entry Delay
must not exceed one (1) minute.
9.6 Cross Zone Time
Enter the time allowed between zone faults. When zones are cross zoned, the same zone
or a second cross zoned zone must fault within this time in order for an alarm report for
both zones to be sent to the receiver. If the cross zone time expires without the second
zone faulting, only a zone fault from the rst zone is reported. Cross-zone time can be
from 4 to 250 seconds. Entering 0 (zero) disables this function. Default is 4.
See the Appendix.
SYSTEM OPTIONS
SYSTEM: AREA
AREA A/P H/A GST
INST ARM NO YES
CLS WAIT NO YES
ENTRY DLY 2: 60
ENTRY DLY 3: 90
ENTRY DLY 1: 30
ENTRY DLY 4: 120
CRS ZONE TM: 4