1912XR Installation Guide
Digital Monitoring Products, Inc. 1912XR Installation Guide
Page 23
26.2 Multiple Indicating circuit modules
AC BELL
AC
1
2
34 56 7 89
10
11
12
13
14 15
16
17 18 19
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power Input
Bell Output +
Bell Output -
Bell Trouble
Bell Trouble
GND
RED YEL GRN BLKB + B - SMK L5+ L5- L1 L2 L3 L4GNDGND
AUXILIARY
POWER
SUPPLY
24 VDC 5 Amp
Maximum
Power Supply
Trouble Contacts
N/C
UL Listed, Polarized
Indicating Devices.
10k EOL Resistor
DMP Model 308
Indicating Circuit Module
DMP Model 866
37mA at 12 VDC
The Auxiliary Power Supply and Indicating
Circuit Module trouble contact Loop must
be programmed as a Supervisory Type Loop
and must be selected for display in the
keypad status list.
See section 10.6 in the 1912XR
Programming Manual (LT-0171).
1k
3.3k Resistor
DMP Model 309
1k
1k
NOTE: If an auxiliary supply is not used,
terminals 3 and 4 on the 866 Indicating
Circuit Module can be jumpered together
to supply bell power from the 1912XR panel.
A maximum of 1 Amp at 12 VDC is available
from terminal 5 of the 1912XR.
Auxiliary power supply must be regulated
UL listed for Fire Protection Signaling Service.
Power supplies must have battery backup.
J4
Dual Line Expansion
J10
Battery Only Restart
J16
Command Processor Reset
UL Listed, Polarized
Indicating Devices.
10k EOL Resistor
DMP Model 308
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power Input
Bell Output +
Bell Output -
Bell Trouble
Bell Trouble
AUXILIARY
POWER
SUPPLY
Power Supply
Trouble Contacts
N/C
24 VDC 5 Amp
Maximum
1k
To additional fourteen 866 Indicating Circuit
Modules. Up to a maximum of sixteen 866
modules on the 1912XR panel. All modules
must be installed in a listed enclosure
connected by conduit and located in the
same room.
Each 866 Indicating Circuit
Module in alarm draws up to
35mA from its terminal 3 alarm
input.
EPROM Socket
Indicating Circuit Module
DMP Model 866
37mA at 12 VDC