1912XR Installation Guide
Digital Monitoring Products, Inc. 1912XR Installation Guide
Page 19
UNIVERSAL UL and NFPA FIRE ALARM SPECIFICATIONS
22.1 Introduction
The programming and installation specifications contained in this section must be completed when
installing the Model 1912XR in accordance with any of the UL or NFPA fire standards. Additional
specifications may be required by a particular standard.
22.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.
22.3 Transformer
A wire-in transformer should be used. Use the 16.5 VAC Model 320 at 40VA or Model 322 at 100VA.
22.4 End of Line resistor
The DMP Model 310 1K EOL resistor should be used on all 1K EOL fire loops.
22.5 System trouble display
The Status List Display must include at least one keypad that displays system monitor troubles. See
section 10.3 of the 1912XR Programming Manual (LT-0171).
22.6 Fire display
The Status List Display must include at least one keypad that displays troubles and alarms on fire type
loops. See section 10.4 of the 1912XR Programming Manual (LT-0171).
22.7 Police station phone number
The digital dialer telephone number programmed for communication must not be a police station phone
number, unless that phone number is specifically provided for that purpose.
22.8 System maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the
end user is essential to ensure continuous satisfactory operation of any alarm system. Offering a
maintenance program and acquainting the user with the correct procedure for use and testing of the
system is also the responsibility of the installing alarm company.
22.9 Audible alarm
Fire Type loops should be programmed to activate an audible alarm. The Bell Action for Fire Type loops
should not be programmed as “N”. See section 8.4A in the 1912XR Programming Manual (LT-0171).
22.10 Fire loop programming
Fire loops must be programmed to activate a trouble on open conditions and an alarm on short conditions.
The swinger bypass function must not be used on any fire loops. If a retard is used on a waterflow loop it
cannot exceed 60 seconds and any retard in the waterflow initiating devices must be subtracted from the
60 seconds allowed. See sections 12.7 and 12.17 in the 1912XR Programming Manual (LT-0171). The
retard delay should not be used on a loop with smoke detectors.
22.11 Model 774 keypad
The fire key in the upper right corner of the 774 keypad is not intended to replace a manual pull station.
22.12 Style D loops
If required, the Radionics D129 Dual Style D Initiating Module provides for connection of two Style D loops
to the Model 1912XR. See section 26.4 and the D129 Installation Instructions for wiring information.
22.13 Video option
The video option must be selected as NO when any fire protection is connected to the 1912XR. See
section 7.9 in the 1912XR Programming Manual (LT-0171).