Digital Monitoring Products, Inc. 1912XR Installation Guide
Page 16
1912XR Installation Guide
UNIVERSAL UL BURGLARY SPECIFICATIONS
17.1 Introduction
The programming and installation specifications contained in this section must be completed when
installing the 1912XR panel in accordance with any of the UL burglary standards. Additional specifications
may be required by a particular standard.
17.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70, UL 681, and UL 611 for all burglary
installations.
17.3 Control outside of protected area
A Potter EVD or Sentrol 5402 should be used in place of a lined cabinet when the panel is installed
outside of the protected area.
17.4 Police station phone numbers
The digital dialer telephone number programmed for communication must not be a police station phone
number, unless that phone number is specifically provided for that purpose.
17.5 Bypass reports
The bypass reports option must be programmed as YES for all UL burglary applications. See section 6.3 of
the 1912XR Programming Manual (LT-0171).
17.6 System maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the
end user is essential to ensure continuous satisfactory operation of any alarm system. Offering a
maintenance program and acquainting the user with the correct procedure for use and testing of the
system is also the responsibility of the installing alarm company.
17.7 Partitions
The partition option may only be used for UL burglary applications when all partitions are used for one
subscriber. See section 4.2 and 11.2 of the 1912XR Programming Manual (LT-0171). The panel must be
tamper protected and Sentrol Model 5402 or Potter EVD listed vibration detectors should be used.
17.8 Cross zoning
Loops used for cross zoning must be installed to allow detection of the same event. For example, two
motion detectors in the same hallway.
UL 1023 SPECIFICATIONS
Household Burglar-Alarm System Units
18.1 Bell cutoff
The bell cutoff time cannot be less than five minutes. See section 8.2 of the 1912XR Programming Manual
(LT-0171).
18.2 Entry delay
The maximum entry delay used must not be more than 45 seconds. See section 7.3 of the 1912XR
Programming Manual (LT-0171).
18.3 Exit delay
The maximum exit delay used must not be more than 60 seconds. See section 11.4 of the 1912XR
Programming Manual (LT-0171).
18.4 Weekly test
The product should be tested weekly.