Digital Monitoring Products XRSuper6/XR20/XR40 Programming Guide
32
zone informaTion
11.11
ALARM ACTION . . .
Alarm Action
The Alarm Action section allows you to change or conrm the default alarm
characteristics of a zone type.
If you selected the non-24-hour zone type Blank, Night, Day, Exit, Auxiliary 1, or
Auxiliary 2, the Alarm Action programing begins with Disarmed Open.
If you selected the 24-hour zone type Fire, Panic, Emergency, or Supervisory, the
Alarm Action programming begins with Armed Open.
The Fire Verify zone type functions the same as Fire Type, with the following
exceptions: When a Fire Verify zone is placed into shorted condition, the panel
performs a Sensor Reset and does not send a report. If any Fire Verify or Fire zone
initiates an alarm within 120 seconds after the reset, an alarm is indicated. If an
alarm is initiated after 120 seconds, the cycle is repeated. If no other Fire Verify or
Fire zone is alarmed within 120 seconds, a zone fault report is sent to the receiver.
11.12
DISARMED OPEN
Disarmed Open
Denes the action taken by the panel when the zone is opened while the area is
disarmed. There are three actions to dene:
Message to Transmit
Output Number
Output Action
You must also make these selections for the Disarmed Short, Armed Open, and
Armed Short zone conditions. Press the COMMAND key to continue.
11.12.1
MSG: TROUBLE
Message To Transmit
You can send two report types to the receiver: Alarm and Trouble. These are
represented by the characters A and T. Press any Select key to display the zone
report options.
A T L -
ALARM - Selecting A allows an alarm report to be sent to the receiver and the bell
output to activate according to zone type. See the Bell Action section. The zone
name appears in the panel’s alarmed zones status lists.
TROUBLE - Selecting T allows a trouble report to be sent to the receiver and the
zone name to appear in the panel’s alarmed zones status lists.
LOCAL - When you select L, an alarm report is NOT sent to the receiver. The bell
output still activates according to zone type and the zone name appears in the
panel’s alarmed zones status lists. NOTE: If Pager is YES in Communication, the
alarm report is also sent to the designated pager.
(dash) - When you select , reports are NOT sent to the receiver. The bell output
does not activate and there is no display in the panel’s alarmed zones status list.
Only the programmed Output Number activates.
11.12.2
OUTPUT NO: 0
Output Number
You can specify any of the outputs on the XRSuper6/XR20/XR40 to be activated by
a zone condition. The output can be activated regardless of the report to transmit
or whether or not the zone is programmed as local. An output activated by a
non-24-hour armed zone is turned off when the zone’s area is disarmed by a user.
To enter an Output Number, press any Select key followed by the output number 1
to 4. Press the COMMAND key.