Installation
XRSuper6/XR20/XR40 Installation Guide
16
Digital Monitoring Products www.dmpnet.com 2500 N. Partnership Boulevard Springfield, MO 65803
UNIVERSAL UL and NFPA FIRE ALARM SPECIFICATIONS
20.1 Introduction
The programming and installation specifications contained in this section must be completed when installing the
Model XRSuper6/XR20/XR40 in accordance with any of the UL or NFPA fire standards. Additional specifications
may be required by a particular standard.
20.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.
20.3 Police station phone number
The digital dialer telephone number programmed for communication must not be a police station phone number,
unless that phone number is specifically provided for that purpose.
20.4 System maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end user
is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance program
and acquainting the user with the correct procedure for use and testing of the system is also the responsibility of
the installing alarm company.
20.5 Audible alarm
Fire Type zones should be programmed to activate an audible alarm. The Bell Action for Fire Type zones should
not be programmed as “N”. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
20.6 Fire zone programming
Fire zones must be programmed to activate a trouble on open conditions and an alarm on short conditions. The
swinger bypass function must not be used on any fire zones. See the XRSuper6/XR20/XR40 Programming Guide
(LT-0305).
20.7 Ground Start
Ground Start phone lines must not be used for UL listed systems.
20.8 UL Listed Receivers
UL has verified operation with the DMP SCS-1 Security Receiver, Sur-Gard SG-HLR2-DG, FBII CP220PB, Osborne-
Hoffman Quick-Alert and Radionics D6500 receivers.
UL 985 NFPA 72 (chapter 2) SPECIFICATIONS
Household Fire Warning System Units
21.1 Bell output definition
The bell output of the Model XRSuper6/XR20/XR40 must be programmed to operate steady on burglary alarms
and pulsed on fire alarms. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
21.2 Indicating Circuit Supervision
The DMP Models 865 and 866 Notification Circuit Module must be used on the bell circuit for detection of shorts
and grounds.