XR500 Series Canadian Installation Guide Digital Monitoring Products
31
Wiring Diagrams
26.5 Canadian Fire Communicator for FACP
AC
12345678 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GND SMK GNDRED YEL GRN BLKZ1Z2Z3Z4Z5Z6Z7Z8 Z9+ Z9- Z10+ Z10-AC -B GND GND GNDGND
K6
K7
Output 1
Output 2
J3
Phone Line
J10
J22
LX-Bus
Battery
Start
J23
J21
RS-232
Power LED
J8
PROG
J4
Tamper
Out2
J2
J1
Ethernet
POWER
TROUBLE
ALARM
COMMAND
1234
5678
90
ABC DEF GHI JKL
MNOPQR STU VWX
YX
ENABLE
SILENCE
RESET
TEST
DRILL
Fire Command Center
630F Annunciator
Standy
Batteries
To FTA7516
transformer
Model 311
1K EOL
XR500 Series
Command Processor™ Panel
Program Bell Options
fire type as None.
Do not use Bell
Output.
J12
75VA
50VA
Program Zone 1 Fire Alarm Zone as type FI and set Fire Panel
Slave Input option as YES.
Program Zone 2 Fire Zone trouble as type FI.
Program Zone 3 AC Trouble zone as type SV and set the Latch
Supervisory option in System Options as NO.
Program Zone 4 Supervisory zone as type SV and set the Latch
Supervisory option in System Options as NO.
Main Fire Alarm
Control Panel (FACP)
{
{
{
Normally Open
Common
Normally Closed
Normally Open
Normally Open
Common
Common
Normally Closed
Normally Closed
Zone Alarm
Form C alarm contacts
activate short on Zone Alarm.
Zone Trouble
Form C trouble contacts activate
open on Trouble condition.
AC Trouble (optional)
Form C contacts activate open on
AC Trouble condition.
Supervisory
Form C contacts activate short on
Supervisory condition.
{
Normally Open
Common
Normally Closed
1.0k Ohm EOL
1k Ohm EOL
Zone 1
Zone 2
Zone 3
1k Ohm EOL
1k Ohm EOL
Zone 4
Auxiliary power
terminal max
500 mA.
Communication Fail
Output 1 must be programmed as a
Comm Fail output in Output Options.
See the ULC S559-04
Specification, located
in the Compliance
section, for more
information.
Must be installed in
conduit and located
within 20 feet.
26.6 Combination S304 and S559 System
XR500 Series
Command Processor™
Panel
AC
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 199 20 21 22 23 24 25 26 27 28
+B BELL GND SMK GNDRED YEL GRN BLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+ Z9– Z10+ Z10–AC –B GND GND GNDGND
K6 K7
Output 1 Output 2
J3
Phone Line
J10
J22
LX-Bus
Battery
Start
Power
LED
J8
PROG
J4
Tamper
J16
Reset
Out1 Out2
Outputs 3-6
J11
3
4
5
6
J2
J1
Ethernet
Network
Communication
To panel
Keypad
or LX-Bus
Relay contacts to
panel zones
Burglary inputs
No Fire Devices
See 21.5 Zone Expansion for a
list of approved expanders
Main Fire Alarm Control
Panel (FACP)
{
{
{
Normally Open
Common
Normally Closed
Normally Open
Normally Open
Common
Common
Normally Closed
Normally Closed
{
Normally Open
Common
Normally Closed
J6 Interface