InstallatIon
Powered Zones for 2-Wire Smoke Detectors
11.1 Terminals 25–26 and 27–28
Panel terminals 25 through 28 provide two resettable Class B, Style A, 2-wire powered zones. For programming
purposes the zone numbers are 9 and 10.
Note:Themaximumwirelengthforeitherzone9orzone10is3000feetusing18AWGor1000feetusing22
AWG.Themaximumvoltageis14Vdcandthemaximumnormalstandbycurrentis1.25mADC.Themaximumline
impedance is 100 Ohms. The maximum short circuit current is 56mA.
Whenusingallotherzoneexpansionmodules,uselistedModel309EOLresistors.Thecompatibilityidentierforthe
zones is A.
Note: Do not mix detectors from different manufacturers on the same zone.
Caution: Performing a Sensor Reset momentarily drops power to the devices on Zones 9 and 10. The panel
views these zones (9 and 10) as “Open” while the power is absent.