
Digital Monitoring Products XR500 Series Canadian Installation Guide
14
InstallatIon
Protection Zones
10.1 Terminals 13–24
Zones1to8(terminals13to24)ontheXR500Seriespanelareallgroundedburglaryzones.Forprogramming
purposes,thezonenumbersare1through8.Listedbelowareterminal13to24connectionfunctions.
Terminal Function Terminal Function
13 Zone 1 voltage sensing 19 Zone 5 voltage sensing
14 GroundforZones1and2 20 GroundforZones5and6
15 Zone 2 voltage sensing 21 Zone 6 voltage sensing
16 Zone 3 voltage sensing 22 Zone 7 voltage sensing
17 GroundforZones3and4 23 GroundforZones7and8
18 Zone4voltagesensing 24 Zone 8 voltage sensing
The voltage sensing terminal measures the voltage across a 1k Ohm End-of-Line resistor to ground. Use DMP Model
311 1k Ohm resistors. Dry contact sensing devices can be used in series (normally-closed) or in parallel (normally-
open) with any of the burglary protection zones.
10.2 Operational Parameters
Each protection zone detects three conditions: Open, Normal, and Short. Listed below are voltage and resistance
parameters for each condition:
Condition Resistance on zone Voltage on positive terminal
Open over 1300 ohms over 2.0 Vdc
Normal 600 to 1300 ohms 1.2 to 2.0 Vdc
Short under 600 ohms under 1.2 Vdc
10.3 Dual EOL
TheXR500SeriesCanadianpanelsupportstheuseofdual1KEOLresistorsonpanelzonesoneto
eight. Two EOL resistors are used so a wire trouble can be indicated during the disarm period.
Whendualend-of-lineoperationischoseninpanelprogramming,normalzoneprocessingoccurs
withthefollowingexception:Whenprocessinganopenzoneandatroubleoralarmmessageis
NOT programmed to be sent for the open state, the panel checks to see if the wire is cut. If the
wire is cut, the panel automatically sends an alarm if armed or trouble is disarmed.
ZONE STATUS
Zone Wires Open Zone Wires Short Contact Normal Contact Open
Disarmed Trouble Trouble Normal Normal
Armed Alarm Alarm Normal Alarm
10.4 Zone Response Time
A condition must be present on a zone for 500 milliseconds before it is detected by the XR500 Series panel. Ensure
detection devices used on the protec tion zones are rated for use with this delay. Zones 1-10 can also be programmed
for a fast response delay of 160 milliseconds.
10.5 Keyswitch Arming Zone
A keyswitch on an Arming type zone allows selected areas to arm and disarm without having to enter a user code.
Figure 7: Protection Zone Wiring
1K Ohm
Normally
Closed
1K Ohm
Normally Open
1K Ohm
Combination Normally Open
and Normally Closed
1K Oh
1K Ohm
m
Indicating Device
Zone wires
to Panel
Zones 1-8
Kommentare zu diesen Handbüchern