Digital Monitoring Products, Inc.
1912XR Programming
Page 22
12.1 AREA INFORMATION - Allows you to assign functions to the different areas
within a partition. All non-24 hour loops must be assigned to an active area. See
Loop Information in section 13.1.
You activate an area by assigning it a name. See section 12.13. A name is given
to each active area in place of a number to assist the user during arming and
disarming.
12.2 PARTITION NUMBER - Enter the partition number to program. Partition 1 using
area arming can have up to eight areas on the 1912XR panel. Partitions 2, 3, and
4 using area arming can each have up to four independent areas.
This prompt is not displayed if you only entered one partition in Device Setup.
12.3 MODE - This option allows you to program how the areas in this partition
operate. The options you can choose are:
AREA ARMING - in which all areas of the partition can be programmed and
operated independently. Partition 1 provides up to eight areas and partitions 2 to
4 each provide up to four areas.
ALL/PERIMETER - in which only areas one and two are activated and operate as
a perimeter and interior system only.
HOME/AWAY - in which three areas can be used: Perimeter, Interior, and
Bedrooms. If you assign loops to the Bedrooms area, the keypad display shows
HOME SLEEP AWAY when the user goes to arm the system. If you do not
assign loops to the Bedrooms area, the keypad only displays HOME AWAY to
the end user.
With the HOME SLEEP AWAY option, the user can:
1. Select HOME to arm just the perimeter.
2. Select SLEEP to arm the perimeter and interior (non bedroom areas).
3. Select AWAY to arm all three areas.
12.4 EXIT DELAY - Enter the exit delay time for all exit type loops in this partition.
When the exit delay time starts, all activity on that loop and other non-24 hour
loop types in the area are ignored until the exit delay expires. This delay
countdown is displayed on the keypad. If an exit type loop is placed in a bad
condition at the end of the exit delay, the system sounds the alarm bell for 15
seconds and sends an exit error report to the alarm receiver. The output cannot
be turned on from the Outputs On/Off option of the User Menu.
If any other loop type is placed in a bad condition at the end of the exit delay an
alarm is indicated. The exit delay can be from 1 to 250 seconds. Enter zero to
disable the Exit Delay feature.
12.5 BURGLARY OUTPUT - This output is turned
on
any time a burglary type loop in
this partition is placed in alarm. The output is turned
off
by a Cutoff Time (see
section 8.5B) or when you disarm the area in which the alarm occurred and no
other burglary type loops are in alarm. Outputs can also be turned off by a user
through the Alarm Silence and Outputs On Off User Menu options.
12.6 OPENING/CLOSING REPORTS - This option allows an Opening report to be
sent to the SCS-1 Receiver whenever an area within this partition is disarmed.
A Closing report is also sent to the SCS-1 Receiver when any area within this
partition is armed.
PARTITION NO: 1
MODE: AREA SYS
AREA A / P H / A
AREA INFORMATION
EXIT DELAY: 45
OPN/CLOS YES
BURGLARY OUT: 0
12-AREA INFORMATION