XRSuper6/XR20/XR40 Installation Guide Digital Monitoring Products
19
ComplIanCe
Universal Fire Alarm Specications
22.1 Introduction
The programming and installation specications contained in this section must be completed when installing
the Model XRSuper6/XR20/XR40 in accordance with any of the UL or NFPA re standards. Additional
specications may be required by a particular standard.
22.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.
22.3 Police Station Phone Number
The digital dialer telephone number programmed for communication must not be a police station phone
number, unless that phone number is specically provided for that purpose.
22.4 System Maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end
user is essential to ensure continuous sat isfactory operation of any alarm system. Offering a maintenance
program and acquainting the user with the correct procedure for use and testing of the system is also the
responsibility of the installing alarm company.
22.5 Audible Alarm
Fire Type zones must be programmed to activate an audible alarm. The Bell Action for Fire Type zones must
not be programmed as N (None). See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
22.6 Fire zone programming
Fire zones must be programmed to activate a trouble on open conditions and an alarm on short conditions.
The swinger bypass function must not be used on any re zones. See the Programming Guide (LT-0305).
22.7 Ground Start
Ground Start phone lines must not be used for UL listed systems.
22.8 Listed Receivers
Operation has been veried with the DMP SCS-1R Security Receiver, Sur-Gard MLR2-E, SG-HLR2-DG, FBII
CP220PB, Osborne-Hoffman Quick-Alert, and Radionics D6500 receivers.
ANSI/UL 985 NFPA 72 (Chapter 2) Specications
Household Fire Warning System Units
23.1 Bell Output Denition
The bell output of the Model XRSuper6/XR20/XR40 must be programmed to operate steady on burglary
alarms and pulsed on re alarms. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
23.2 Indicating Circuit Supervision
The DMP Models 865 and 866 Notication Circuit Module must be used on the bell circuit for detection of
shorts and grounds.
23.3 Wireless External Contact
When used, the External Contact of 1101, 1102, or 1103 must be programmed Normally Closed. See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
23.4 Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes. See the XRSuper6/XR20/XR40 Programming
Guide (LT-0305).
23.5 Wireless Fire Verication
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verication
(FV) zone type. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
California State Fire Marshal Specications
24.1 Bell Output Denition
The bell output of the Model XRSuper6/XR20/XR40 must be programmed to operate steady on burglary
alarms and temporal on re alarms. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).