Digital Monitoring Products XRSuper6/XR20/XR40 Installation Guide
18
ComplIanCe
ANSI/UL 609 Specications
Local Burglar Alarm Units and Systems
21.1 Entry Delay
The maximum entry delay must not exceed 60 seconds with the Model 350A housing. See LT-0305.
21.2 Bell
A local audible signal appliance must be used.
In a mercantile burglar alarm system, a mercantile alarm sounding device located within a building but
outside the protected area, is acceptable, provided it is rated for outside service and alarm conditions are
transmitted to:
a) The dispatch location of the law enforcement agency having jurisdiction over the protected property or
b) A central station or residential monitoring station complying with the Standard for Central Station Alarm
Services, UL 827.
In a mercantile burglar alarm system, an alarm sounding device located within the area of greatest
protection, or outside the area of greatest protection but within an area protected by an alarm system and
that shares a common control unit with the system installed in the area of greatest protection, is acceptable
provided it is rated for inside service and alarm conditions are transmitted to:
a) The dispatch location of the law enforcement agency having jurisdiction over the protected property or
b) A central station or residential monitoring station complying with the Standard for Central Station Alarm
Services, UL 827.
An inside sounding device shall be mounted at least 10 feet (3.05 m) above the oor or at the surface of the
ceiling. When there is xed construction within the area that could provide access for an intruder, the alarm
sounding device shall also be mounted at least 4 feet (1.2 m), as measured horizontally, away from the
edges of the xed construction or at least 10 feet (3.05 m) above it so as to minimize access by an intruder.
21.3 Bell Cutoff
The bell cutoff time cannot be less than 15 minutes. See the Programming Guide (LT-0305).
21.4 Automatic Bell Test
The Automatic Bell Test option must be programmed as YES. See the Programming Guide (LT-0305).
21.5 Mercantile Safe and Vault
When the DMP Model 350A housing is used, the panel provides operation as a mercantile safe and vault
alarm. Bell Supervision and wiring must be in accordance with UL 681. If the panel is mounted outside the
safe or vault, tamper protection and the Sentrol Model 5402 or Potter EVD listed vibration detectors should
be used. The XRSuper6/XR20/XR40 does not provide operation as a Bank Safe and vault alarm.
21.6 Wireless Arming Mode
The System Options Mode for arming must be programmed as Area or All/Perimeter (A/P). See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
21.7 Wireless Tamper
The Zone Information Disarmed Open Message to Transmit must be programmed Trouble (T). See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
21.8 Wireless External Contact
When used, the External Contact of 1101, 1102, or 1103 must be programmed Normally Closed. See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
21.9 Wireless Supervision Time
The Zone Information Supervision Time cannot be set to 0 (zero). See the XRSuper6, XR20, XR40
Programming Guide (LT-0305).
21.10 Wireless Audible Annunciation
The Wireless Audible option must be selected as ANY for commercial applications.