12.13 FA426 Wireless Operation
The FA426 is a 900MHz wireless receiver that installs in the enclosure of the XRSuper6/XR20/XR40
Command Processor and allows you to add up to 16 wireless expansion zones to the panel. A wire
harness included with the FA426 plugs into the receiver and connects to the keypad bus terminals on
the panel.
Wireless points 2 through 16 are suitable for use with supervised wireless transmitters on doors or
windows as well as wireless smoke detectors, glassbreak detectors, and PIRs. No response from these
points after four hours is indicated by the panel as Missing.
Point 1 is unsupervised and designated for use with the FA113 Keychain Remote. The FA113 allows the
user to arm and disarm one or more areas of the system without using a keypad. The FA113 also
contains two ALERT buttons that allow the user to initiate a Panic alarm to the system. The
unsupervised feature of point 1 allows the FA113 to be removed from the premises without a Missing
report being generated. You can use any number of FA113 Keychain Remote devices on point 1 to allow
for multiple users.
The FA426 can communicate wireless Alarm, Trouble, Missing, and Low Battery reports to the
XRSuper6/XR20/XR40 panel. The Alarm report is received as a short condition by the panel. The
Trouble report is received as an open condition by the panel. Zone information programming in the
XRSuper6/XR20/XR40 panel must be configured for these conditions. Missing and Low Battery reports
require no special programming.
Low Battery note: If a Low Battery condition on a transmitter is corrected by replacing the battery, a
Sensor Reset must be performed on the XRSuper6/XR20/XR40 system to clear the Low Battery message
from the keypad Status List.
FA426 connection to panel: If the connection between the FA426 and the panel is broken, zones
monitored by the FA426 will report an open condition.