Digital Monitoring Products XR2500F Installation Guide
36
CoMPlIanCe
Universal Fire Alarm Specications
34.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstalling
theModelXR2500FinaccordancewithanyoftheANSI/ULorNFPArestandards.Additionalspecications
mayberequiredbyaparticularstandard.SeetheXR500SeriesProgrammingGuide(LT-0679).
34.2 Wiring
AllwiringmustbeinaccordancewithNEC,ANSI/NFPA70.
34.3 Transformer
Usethesupplied16VAC56VAtransformer.
34.4 End-of-Line Resistor
TheDMPModel3101KOhmEOLresistorshouldbeusedonall1KOhmEOLrezones.
34.5 System Trouble Display
TheStatusListDisplaymustincludeatleastonekeypadthatdisplayssystemmonitortroubles.
34.6 Fire Display
TheStatusListDisplaymustincludeatleastonekeypadthatdisplaystroublesandalarmsonretypezones.
34.7 Police Station Phone Number
Thedigitaldialertelephonenumberprogrammedforcommunicationmustnotbeapolicestationphone
number,unlessthatphonenumberisspecicallyprovidedforthatpurpose.
34.8 System Maintenance
Toensurecontinuoussatisfactoryoperationofanyalarmsystem,properinstallationandregular
maintenancebytheinstallingalarmcompanyandfrequenttestingbytheenduserisessential.Offeringa
maintenanceprogramandacquaintingtheuserwiththecorrectproceduresforsystemuseandtestingis
alsotheresponsibilityoftheinstallingalarmcompany.
34.9 Audible Alarm
FireTypezonesmustbeprogrammedtoactivateanaudiblealarm.TheBellActionforFireTypezonesmust
notbeprogrammedas“N”.
34.10 Fire Zone Programming
Ifaretarddelayisusedonawaterowzone,itcannotexceed90secondsandanyretarddelayinthe
waterowinitiatingdevicesmustbesubtractedfromthe90secondsallowed.Theretarddelayshouldnotbe
usedonazonewithsmokedetectors.
34.11 Style D Zones
Ifrequired,theDMP869DualStyleDInitiatingModuleprovidesforconnectionoftwoStyleDzonestothe
ModelXR2500F.Seethe869InstallationGuide(LT-0186)andthisguideforwiringinformation.
34.12 Listed Receivers
UsetheDMPSCS-1R(SDLC),Sur-GardSG-HLR2-DG(CID),FBIICP220PB(CID),andOsborne-HoffmanQuick-
Alert(CID)receivers.